Lennox furnace error codes

170 codes with causes and test steps, plus 5 settings tables.

CodeMeaningSeverity
1 flashLine voltage polarity reversedMedium
2 flashesImproper earth groundMedium
3 flashesBurner failed to light or lost flameHigh
4 flashesLow flame signalMedium
5 flashesWatchguard - ignition retries/recycles exceededHigh
7 flashesPrimary or secondary limit openHigh
8 flashesRollout switch openCritical
9 flashesPressure switch stays open or drops out on a heat callHigh
10Unknown device detectedHigh
10 flashesWatchguard - pressure switch opened 5 times in one heat demandHigh
11Missing deviceHigh
11 flashesPressure switch stuck closed before inducer startsMedium
12Indoor unit not detectedHigh
12 flashesFlame sensed with gas valve offCritical
13Duplicate comfort sensor IDHigh
13 flashesLow line voltageMedium
14Too many devices of the same typeHigh
15Parameter mismatch detectedLow
20Protocol upgrade requiredHigh
21Incompatible equipment detectedHigh
29Over temperature protection (indoor above 90 F)High
30Low temperature protection (below 40 F)High
31Lost communication with deviceHigh
32Device resettingLow
34Must program unit capacity for deviceHigh
35Incorrect operation of deviceHigh
36Heating when not requestedHigh
37Cooling when not requestedHigh
38Not heating when requestedHigh
39No cooling when requestedHigh
40HP heating lockoutLow
41Device control board replacedLow
500PureAir differential pressure sensor faultMedium
501PureAir UV sensor faultMedium
502PureAir UV lamp offMedium
503PureAir filter life at 10%Medium
504PureAir filter life at 0%Medium
505PureAir model selection changedMedium
506PureAir lamp at 0% lifeMedium
507PureAir filter calibration failureMedium
530Zoning low damper 24 VACMedium
532Zoning pressure switch opened (high pressure)Low
542Zone 1 temperature sensor faultMedium
543Zone 2 temperature sensor faultMedium
544Zone 3 temperature sensor faultMedium
545Zone 4 temperature sensor faultMedium
546Zone sensor parameters reset after power restoreMedium
547Zone sensor parameters reset from system interruptionMedium
548Zone humidity sensor errorMedium
551Zone sensor lost communicationMedium
610Low room temperature detectedHigh
700Thermostat temperature sensor problemHigh
701Thermostat temperature above limitHigh
703Thermostat humidity sensor problemMedium
3000Replace filter 1Low
3001Replace filter 2Low
3002Replace humidifier padLow
3003Replace UV bulbLow
3004Maintenance reminderLow
3005PureAir maintenanceLow
65537Missing base (smart hub)High
65538Missing baseLow
65539Thermostat lost connection or internal faultHigh
65540Missing HD wall displayLow
65541Firmware download failedLow
65542Firmware update failedLow
65543Firmware updatedLow
65544More than 8 thermostats in a groupLow
70001IAQ internal sensor faultMedium
70002IAQ internal data faultMedium
70003IAQ side switch in OFF positionHigh
70004Replace Smart IAQ monitorMedium
70501Smart room sensor internal data faultMedium
70502Smart room sensor internal faultMedium
70503Smart room sensor low batteryLow
70504Smart room sensor battery 1%Low
71001Wireless extender internal data faultMedium
71511Duct or filter blockageMedium
71517Indoor fan motor failureHigh
80001IAQ persistent poor air qualityLow
80002Unresponsive wireless device faultLow
80003Lost communication with wireless deviceMedium
80005Unknown wireless device foundMedium
E105Device communication problemHigh
E106Twin communication faultMedium
E110Low line voltageHigh
E111Line voltage polarity reversedHigh
E112Ground not detectedHigh
E113High line voltageHigh
E114Line frequency out of rangeHigh
E115Low 24 VACHigh
E116High 24 VACHigh
E117Poor ground detectedMedium
E120Unresponsive deviceMedium
E124Lost communication with thermostatHigh
E125Control hardware failureCritical
E126Control internal communication problemHigh
E130Configuration jumper missingHigh
E131Corrupted control parametersHigh
E132Device control software faultHigh
E150A2L refrigerant leak alarmCritical
E151A2L sensor faultHigh
E152Refrigerant leak sensor #2 faultHigh
E154Refrigerant leak sensor #1 communication lost / wrong DIP settingHigh
E155Refrigerant leak sensor #2 communication lostHigh
E160Refrigerant leak sensor #1 wrong typeMedium
E161Refrigerant leak sensor #2 wrong typeMedium
E163Furnace control board failureHigh
E164Low GWP test mode activeLow
E180Outdoor air temperature sensor failureMedium
E200Flame rollout - hard lockoutCritical
E201Indoor blower communication failureHigh
E202Blower motor mismatchHigh
E203Unit capacity not programmedCritical
E204Gas valve miswiredHigh
E205Gas valve relay contact shortedCritical
E206Gas valve second-stage relay failureMedium
E207Hot surface ignitor openHigh
E223Low pressure switch failed openHigh
E224Low pressure switch failed closedHigh
E225High pressure switch failed openHigh
E226High pressure switch failed closedHigh
E227Low pressure switch opened during ignition or runHigh
E228Inducer calibration failureMedium
E229Ignition on high fireLow
E240Low flame current (run mode)Medium
E241Flame sensed out of sequence - flame presentCritical
E250Limit switch circuit openHigh
E252Discharge air temperature too highMedium
E270Soft lockout - no flame after max retriesHigh
E271Soft lockout - retries exceeded, pressure switch openedHigh
E272Soft lockout - recycles exceeded, pressure switch openedHigh
E273Soft lockout - recycles exceeded, flame failureHigh
E274Soft lockout - limit openedHigh
E275Soft lockout - flame out of sequence, now goneCritical
E276Watchguard calibration failureHigh
E290Ignitor circuit faultHigh
E291Heat airflow below minimumHigh
E292Blower motor will not startHigh
E294Inducer over currentHigh
E295Blower motor over temperatureHigh
E310Discharge air sensor failureMedium
E311Heat rate reduced for airflowMedium
E312Restricted airflow in cooling/fanMedium
E313Indoor/outdoor capacity mismatchLow
E331Global network connection problemLow
E334Y1 relay stuck on controlHigh
E344IFC relay Y1 stuckHigh
E345Relay O failureHigh
E347No 24 V on Y1 outputCritical
E348No 24 V on Y2 outputCritical
E349No 24 V between R and OCritical
E370Interlock switch openHigh
E380EIM interlock relay faultHigh
E381EIM interlock relay stuckHigh
E382EIM relay W1 faultHigh
E390Low GWP relay stuckHigh
E400LSOM - compressor internal overloadHigh
E401LSOM - long run or low pressureCritical
E402LSOM - outdoor pressure tripHigh
E403LSOM - compressor short cyclingMedium
E404LSOM - locked rotorHigh
E405LSOM - compressor open circuitHigh
E406LSOM - open start circuitHigh
E407LSOM - open run circuitHigh
E408LSOM - welded contactorHigh
E409LSOM - low secondary voltageHigh
--Double dashes - zone sensor problemMedium
Red LED offNo power to control or board faultHigh
Red LED on steadyBoard fault detected (107163-01)High

Settings and specs

Filter sizes by cabinet width

Filters · Lennox ML180UHE

CabinetSide returnBottom return
A - 14-1/2 in.16 x 25 x 1 (1)14 x 25 x 1 (1)
B - 17-1/2 in.16 x 25 x 1 (1)16 x 25 x 1 (1)
C - 21 in.16 x 25 x 1 (1)20 x 25 x 1 (1)
D - 24-1/2 in.16 x 25 x 1 (2)24 x 25 x 1 (1)
  • Filters are field supplied; check monthly.
  • Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.

Source: Lennox ML180UHEK Unit Information 100161/100166, Table 16, p.30

Filter sizes (filter rack kits)

Filters · Lennox EL195UHNE

CabinetHorizontal end rackSide return rack
B width (040, 060)18 x 25 x 1 (kit 87L96)16 x 25 x 1 (kit 44J22)
C width (080, 100)20 x 25 x 1 (kit 87L97)16 x 25 x 1 (kit 44J22)
  • Filters are field supplied; check monthly.
  • 100NE60C over 1800 cfm with single side return needs a 20 x 25 x 1 filter via return air base and transition.

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Optional Accessories, p.3

Filter sizes by cabinet width

Filters · Lennox SL297NV

CabinetSide returnBottom return
17-1/2 in. (040, 060)16 x 25 x 1 (1)16 x 25 x 1 (1)
21 in. (080)16 x 25 x 1 (1)20 x 25 x 1 (1)
  • No filter or rack supplied; use a field high-velocity rated filter and keep one in place whenever the unit runs.

Source: Lennox SL297UHNV Installation Instructions 507760-02 (02/2018), Table 1, p.11

Models covered

EL195UH040NE36BEL195UH060NE36BEL195UH080NE48CEL195UH100NE60CEL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DKSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.