Lennox · Furnace
E113 High line voltage
What the control is telling you
Line voltage is above the nameplate rating.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Supply voltage too high
Test and repair steps
- Warning: Use caution when measuring line voltage.
- Measure line voltage and compare to nameplate rating.
- At the integrated control, line hot to line neutral should read 97-132 VAC.
- Have the supply voltage corrected to within range.
- System resumes 5 seconds after the fault clears.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.33; Ignition Control 107045-XX Diagnostic Codes table, p.40, Proper Ground and Voltage p.85. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.