Lennox · Furnace

Red LED off No power to control or board fault

High severity Lennox EL195UHNE

What the control is telling you

Red LED is dark: the control has no power or has detected a board fault.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • No 120 V supply (breaker, switch, door interlock open)
  • Tripped 3 A 24 V circuit breaker CB8
  • Failed transformer T1
  • Failed integrated control

Test and repair steps

  1. Check the blower door is on (door interlock S51 is in series with line voltage).
  2. Check breaker/disconnect and 120 VAC at the control LINE and NEUTRAL terminals.
  3. Check and reset circuit breaker CB8 (3 A at 32 V) in the control box; if it trips again look for a 24 V short.
  4. Check 24 VAC output of the 40 VA transformer.
  5. If power is present and the LED stays off, replace the control.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.