Lennox · Furnace
E116 High 24 VAC
What the control is telling you
Control voltage is above the 18 to 30 volt range.
Applies to: EL296UHV(X) series furnaces with integrated control 103130-XX only
Likely causes
- High line voltage
- Wrong transformer primary tap or wiring
Test and repair steps
- Measure 24 VAC at the control; normal range is 18 to 30 volts.
- Check line voltage to the equipment (120 V).
- Correct the voltage problem; clears when proper voltage is sensed.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.