Lennox · Furnace
E154 Refrigerant leak sensor #1 communication lost / wrong DIP setting
What the control is telling you
The control cannot talk to refrigerant detection sensor #1, or the Low GWP DIP switches do not match the sensors fitted. The blower latches on for at least 5 minutes after communication returns.
Applies to: ML180UHEK (R-454B era) single-stage 80% furnaces with integrated control 107792-XX (ML180UH045/070/090/110/135, incl. low-NOx X models)
Likely causes
- Damaged or unplugged sensor #1 wiring harness or connector
- Sensor #1 damaged or plug obstructed
- LGWP DIP switches set wrong (e.g. Enable with no sensor fitted)
- Furnace-only / R410A job with sensors still enabled
Test and repair steps
- Check the LGWP DIP switches (Table 17) one sensor = LGWP1 Enable / LGWP2 Disable; two sensors = both Enable; no sensor (R410A or heat only) = both Disable. LGWP1 Disable with LGWP2 Enable is invalid.
- On a furnace-only or non-low-GWP job set both switches to Disable, otherwise the blower runs continuously.
- Check the sensor #1 cable is seated in the SENSOR 1 (LGWP1) plug with the Molex clip locked and no dust or moisture.
- Inspect the harness for damage along its route and at the evaporator coil.
- Press the LGWP test button on the control to retest once repaired.
Settings for these units
- Filter sizes by cabinet width · Lennox ML180UHE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox ML180UHEK Unit Information 100161/100166, Table 6 Integrated Diagnostic Codes, p.14; Table 17 LGWP DIP switch settings, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.