Lennox · Furnace

13 flashes Low line voltage

Medium severity Lennox EL195UHNE

What the control is telling you

Line voltage is too low. Below 70 V the control will not answer a heat call until voltage is above 75 V; cooling continues.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Low utility voltage
  • Loose connections or undersized wiring
  • Generator/inverter supply

Test and repair steps

  1. Measure line voltage at the control hot to neutral should be 97-132 VAC.
  2. Check breaker, disconnect and connections for voltage drop under load.
  3. Correct the supply; heating restarts once voltage is back above 75 V.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; flowchart p.51-52. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.