Lennox · Furnace
E226 High pressure switch failed closed
What the control is telling you
High-fire pressure switch is closed when it should be open.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Switch contacts stuck closed
- Jumpered switch
- Wiring short
Test and repair steps
- Warning: Remove any jumper; the pressure switch must never be bypassed.
- The control checks that the pressure switches are open before the inducer starts; a switch closed at that point blocks ignition.
- Check high pressure switch operation at the start of a heat call.
- Check wiring for shorts.
- Measure operating pressure and compare to the set-point tables.
- Check the condensate trap and the condensate hose screens at the cold end header box for blockage (power off; twist and pull screens, rinse); prime the trap with 10 fl. oz. (300 ml) of water if dry. If furnace and coil drains are combined, the A/C drain must be vented or the pressure switch will not work properly.
- Inspect vent and inducer; replace the switch if contacts are stuck.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Troubleshooting: Heating Sequence of Operation flowchart, p.110-112. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.