Lennox · Furnace
542 Zone 1 temperature sensor fault
What the control is telling you
Zone 1 sensor reading out of range or open/short for more than five seconds; zone shows '--', system runs central mode (all dampers open). Escalates after 10 minutes. Thermostat shows 'Problem (Zoning Control)'. S30/S40 thermostat alert code 542.
Applies to: Lennox communicating gas furnaces (e.g. SL280UHV/SL280UHNV, EL296UHV) in S30/S40 smart thermostat systems
Likely causes
- Loose or miswired sensor connections
- Open or shorted sensor
- Two sensors assigned the same zone number
Test and repair steps
- Check sensor and damper control module terminals for loose or incorrect wiring.
- Check zone number assignments; no two sensors may share a number.
- Replace the sensor if open or shorted.
- Clears 30 seconds after the condition ends.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes (filter rack kits) · Lennox EL195UHNE
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.45. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.