Red LED on steady Board fault detected (107163-01)

High severity Lennox EL195UHNE

What the control is telling you

On control 107163-01 a steady (not flashing) red LED means the control found an internal fault. The cooling flowchart also calls a steady LED a circuit board failure.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Failed integrated control

Test and repair steps

  1. Interrupt main power for a few seconds to reset the control.
  2. Check line voltage, polarity and ground; Check ground at the control: AC volts between line neutral and the C terminal should be about 0.3 V (2 V max) at idle, 0.75 V (5 V max) with inducer/ignitor on, under 2 V (10 V max) with blower on; line hot to neutral should be 97-132 VAC.
  3. If the LED stays solid on, replace the integrated control (not field repairable).

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; cooling flowchart p.53. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.