Goodman furnace error codes
19 codes with causes and test steps, plus 4 settings tables.
| Code | Meaning | Severity |
|---|---|---|
| E10 | Grounding fault / poor neutral connection | High |
| E11 | Flame rollout switch open | Critical |
| EE0 | Lockout - too many ignition retries (3) | High |
| EE1 | Pressure switch closed at start of heating cycle | Medium |
| EE2 | Pressure switch did not close (inducer runs, no ignition) | Medium |
| EE3 | High (primary) limit open | High |
| EE4 | Flame sensed with no call for heat | Critical |
| EE5 | Open fuse (short in low voltage wiring) | Medium |
| EE6 | Low flame signal | Low |
| EE8 | High-stage pressure switch closed at start of heating cycle | Medium |
| EE9 | High-stage pressure switch did not close | Medium |
| EEA | Reversed line polarity or grounding error | High |
| EEC | Internal gas valve error - valve energized when it should not be | Critical |
| EEE | Internal control fault (IRQ loss) | High |
| EEH | Twinning error | Low |
| EEJ | Inducer relay error | High |
| EEL | Igniter relay / igniter circuit fault | High |
| EEb | External gas valve error - valve not energized when it should be | High |
| EEn | Igniter open | High |
Settings and specs
Normal status displays (7-segment)
Installer menu · Goodman/Amana GM9S96/AM9S96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
- These are normal operating displays, not fault codes.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Status Codes - Status Menu p.28
Normal status displays (7-segment)
Installer menu · Goodman/Amana GM9S80/AM9S80
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
- These are normal operating displays, not fault codes.
Source: Goodman RS6621008r2 (GM9S80 service), 1 Stage Status Codes - Status Menu p.31
Normal status displays (7-segment)
Installer menu · Goodman/Amana GM9C96/AM9C96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
- These are normal operating displays, not fault codes.
Source: Goodman RS6612020r1 (GM9C96 service), 2 Stage Status Codes p.34
Minimum recommended filter size
Filters · Goodman/Amana GM9C96/AM9C96
| Configuration | Size code | Minimum filter |
|---|---|---|
| Upflow | *0403A* | 1 - 16 x 25 side or 1 - 14 x 24 bottom return |
| Upflow | *0603A* | 1 - 16 x 25 side or 14 x 24 bottom return |
| Upflow | *0603B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0803B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804C* | 1 - 16 x 25 side or bottom return |
| Upflow | *0805C* | 1 - 16 x 25 side or bottom return (see note 1) |
| Upflow | *0805D* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1) |
| Upflow | *1004C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1005C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1205D* | 2 - 16 x 25 side or 1 - 24 x 24 bottom return |
| Downflow | *0403A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
| Downflow | *0603A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
| Downflow | *0804B* | 2 - 14 x 20 or 1 - 16 x 25 top return |
| Downflow | *1005C* | 2 - 14 x 20 or 1 - 20 x 25 top return |
- Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.
- Upflow at 1800 CFM or more: use two side returns or one side plus bottom.
- Larger filters are fine; filters may also be in a central return.
- Horizontal installs: filters must be outside the furnace (central return).
- Filters are not supplied with the furnace; replace every two months or as needed.
Source: Goodman RS6612020r1 (GM9C96 service), Minimum Recommended Filter Size p.16-17
Models covered
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.