Goodman · Furnace
EEL Igniter relay / igniter circuit fault
What the control is telling you
The control detected a problem in the igniter circuit: wiring, a shorted or improperly connected igniter, poor ground, or a failed igniter relay on the board.
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
Likely causes
- Wiring problem between control and igniter
- Shorted or improperly connected igniter
- Poor unit ground
- Igniter relay fault on the integrated control
Test and repair steps
- Check and correct the wiring and plug between the integrated control and the igniter.
- Ohm the igniter at room temperature (37-68 ohms silicon nitride; 30-300 ohms carbide mini igniter on 80% models); replace a shorted igniter.
- Verify the unit ground wire runs back to the panel and the ground connection is tight.
- During igniter warm-up, check for 115 VAC output at the control's igniter terminals; no output with a good igniter and wiring = replace the control board.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.