Goodman · Furnace
EE6 Low flame signal
What the control is telling you
The furnace runs normally but the flame-sense current is weak. If it keeps dropping the furnace will start losing flame and locking out.
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
Likely causes
- Flame sensor coated or oxidized
- Flame sensor not positioned correctly in the flame
- Lazy burner flame from wrong gas pressure or poor combustion air
- Poor ground
Test and repair steps
- Put a DC microamp meter in series with the flame sensor wire and run a heat cycle: normal is 1 to 4 microamps.
- Clean the flame sensor with steel wool (an invisible coating acts as an insulator) and check that it sits in the flame.
- Check the burner flame it should be stable, soft and blue, not lifting or yellow.
- Compare manifold and inlet gas pressure with the rating plate and adjust if needed.
- Inspect the combustion air intake pipe is it blocked, and are its length, elbow count and termination correct?
- Check high-resistance connections and grounding in the flame sense circuit.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36; Checking Flame Sensor p.25-26 (RS6612022r1). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.