Goodman · Furnace

E10 Grounding fault / poor neutral connection

High severity Goodman/Amana GM9S96/AM9S96Goodman/Amana GM9S80/AM9S80Goodman/Amana GM9C96/AM9C96

What the control is telling you

The control detected a grounding error or a poor neutral connection. The furnace will not operate.

Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92

Likely causes

  • Loose or high-resistance neutral connection
  • Missing or poor ground path

Test and repair steps

  1. Check the neutral wire connection at the furnace junction box, the control board and the panel; tighten or repair.
  2. Verify continuity from the furnace to the ground source (ground wire back to the panel).
  3. Power off and measure neutral (white) to burner resistance - it should be very low (manual: less than 2 ohms).
  4. Restore power and confirm the code clears.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.