Rheem · Furnace

68 No blower communication (NO BLWR COMM)

Critical severity RGPE/RGLE

What the control is telling you

IFC cannot communicate with the ECM blower motor. Thermostat also shows Call For Service / CHECK FURNACE to the homeowner.

Applies to: RGPE/RGLE 2-stage 80+

Likely causes

  • Loose/broken IFC-to-ECM communication wiring
  • No power to the motor
  • Failed ECM motor control

Test and repair steps

  1. Check all connections between IFC and ECM motor.
  2. Check 24 V at the ECM 4-pin connector, pins 1 and 4.
  3. Check 115 VAC to the motor and the PFC choke.
  4. Check memory card is correct (blower data, see d6/d7).
  5. Replace the motor if wiring and power are good.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.