68 No blower communication (NO BLWR COMM)
What the control is telling you
IFC cannot communicate with the ECM blower motor. Thermostat also shows Call For Service / CHECK FURNACE to the homeowner.
Applies to: RGPE/RGLE 2-stage 80+
Likely causes
- Loose/broken IFC-to-ECM communication wiring
- No power to the motor
- Failed ECM motor control
Test and repair steps
- Check all connections between IFC and ECM motor.
- Check 24 V at the ECM 4-pin connector, pins 1 and 4.
- Check 115 VAC to the motor and the PFC choke.
- Check memory card is correct (blower data, see d6/d7).
- Replace the motor if wiring and power are good.
Settings for these units
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.