44 Low pressure switch closed (stuck)

High severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)RGPE/RGLE

What the control is telling you

Low-fire pressure switch (LPC) is closed when it should be open, before the inducer starts. The furnace will not start a heat cycle. RGPE/RGLE: thermostat shows Call For Service.

Applies to: 802P/80MDP (802PA050-150); RGPE/RGLE 2-stage 80+

Likely causes

  • Pressure switch contacts welded
  • Shorted or miswired switch wiring
  • Water in switch or hose

Test and repair steps

  1. With the inducer off, check LPC contacts - must be open.
  2. Check switch wiring for a short.
  3. Check switch and hoses for water or moisture.
  4. Replace the switch if contacts stay closed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; RGPE/RGLE: Table 16 p.49 / Table 20. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.