Rheem · Furnace
13 Flame lost
What the control is telling you
Flame was proven and then lost during the heat call. On 802P/R95P, 5 losses in one call cause a 1-hour lockout (10 and 13 alternate).
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Dirty flame sensor
- Low or fluctuating gas pressure
- Pressure switch dropping out (wind, blocked vent, water in hoses, long vent)
- Poor ground or reversed polarity
- Flame not carrying across all burners
- R95P: limit circuit opening
Test and repair steps
- Clean the flame sensor and check its wire to the IFC.
- Check gas supply and manifold pressure under full fire.
- Check whether a pressure switch opens during the run: hoses, water/moisture, vent blockage or length, high wind, blocked heat exchanger.
- Check L1/neutral polarity and ground.
- Confirm all burners light and stay lit.
- R95P check the limit circuit for opening.
- Lockouts clear when the fault is fixed and power is cycled; a soft lockout can also be cleared by removing the heat call for more than 2 but less than 20 seconds.
Settings for these units
- Clearance to combustibles (all models) · R95P
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40-41, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.