ICP · Furnace
LED off Amber status LED off - no power / blown 3 A fuse
What the control is telling you
The control shows nothing. Usually no 115 V or 24 V at the board, an open door switch, or the 3-amp 24 V fuse is blown.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Blower door switch open
- Breaker off / no 115 V at L1-L2
- Blown 3-amp automotive fuse (24 V short)
- Failed transformer
Test and repair steps
- Warning: Manually closing the door switch exposes live 115 V parts - use caution.
- Check the breaker is on and there is 115 V at L1 and L2 on the control.
- Make sure the blower door is on and the door switch is closed; confirm 115 V reaches the switch, replace switch if power goes in but not out.
- Check for 24 V at SEC-1 and SEC-2; if 115 V is present but no 24 V, replace the transformer.
- If the 3-amp fuse is open, replace it with a 3-amp fuse ONLY, then disconnect thermostat leads to find the short in the 24 V wiring.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.