7 Limit circuit lockout
What the control is telling you
Limit or rollout switch open more than 3 minutes, or 10 limit trips in a row at maximum heat. Auto-resets after 3 hours. Troubleshoot as code 4.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Same causes as code 4 - airflow restriction, blower problem, overfiring, failed limit/rollout
Test and repair steps
- Warning: Find why the limit/rollout opened before resetting - repeated trips mean overheating.
- Follow code 4 checks filter, ducts, blower wheel, gas input, limit switch and gasket.
- Manually reset rollout switch if tripped.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.