Rheem · Heat pump
30 ICC fuse open
What the control is telling you
The 3-amp low-voltage fuse on the ICC is blown.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Shorted, damaged or miswired low voltage wiring at R and C
Test and repair steps
- Warning: Turn power off before working on the control.
- Find and fix the short in the R/C wiring (check for nicked thermostat wire, wires touching the cabinet).
- Replace only with a 3A automotive ATC-style blade fuse.
- Restore power and confirm 24VAC at R-C.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.