Rheem · Heat pump

03 Short cycling

Medium severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

The last four (4) compressor cycles each ran less than three (3) minutes. Reported as 3 flashes on the L terminal.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Loose or bad thermostat wiring (R, C, 1, 2)
  • Thermostat located too close to a supply register

Test and repair steps

  1. Check thermostat wire connections at R, C, 1 and 2 at thermostat, indoor and outdoor unit.
  2. Check the thermostat location - move it if it sits in the discharge air stream of a supply grille.
  3. Check for intermittent pressure control trips (codes 21/29) in fault history.
  4. Check charge and indoor airflow if pressure controls are tripping.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.