Codes / Navien / Tankless water heater
Navien tankless water heater error codes
33 codes with causes and test steps, plus 3 settings tables.
Code Meaning Severity E003 Ignition failure High E004 False flame detection Medium E012 Flame loss High E016 Heat exchanger overheating High E21 No hot water Medium E030 Exhaust overheating High E031 Burner overheating Critical E046 Limit control abnormal High E047 Exhaust thermistor open or shorted Medium E060 Dual venturi abnormal High E109 Fan motor abnormal High E110 Abnormal air pressure High E407 Hot water outlet thermistor open or shorted Medium E421 Cold water inlet 1 thermistor open or shorted Medium E432 Cold water inlet 2 thermistor open or shorted Medium E434 Water adjustment valve abnormal Medium E438 Circulation pump abnormal (with air handler) Medium E439 Flow sensor abnormal Medium E441 Hot water inlet 2 thermistor open or shorted Medium E445 Bypass mixing valve abnormal Medium E515 PCB abnormal High E517 DIP switch setting abnormal Medium E593 Front panel key abnormal Low E594 EEPROM abnormal High E615 Input and memory abnormal High E736 Cascade communication abnormal Medium E740 Outdoor temperature sensor abnormal (with air handler) Low E760 Flushing / service alarm Low E762 Vent pipe not properly inserted High E773 Wrong gas type detected Critical E782 Main / panel communication abnormal Medium E785 Flow switch / sensor abnormal (with air handler) Medium E788 Gas type mismatch: DIP switch vs panel setting Medium
Settings and specs
Installation clearances (indoor / outdoor)
Clearances · Navien NPE-2
Side Indoor Outdoor Top 9 in. (229 mm) 36 in. (900 mm) Back 0.5 in. (13 mm) 0.5 in. (13 mm) Front 4 in. (100 mm) 24 in. (600 mm) Sides 3 in. (76 mm) 3 in. (76 mm) Bottom 12 in. (300 mm) 12 in. (300 mm)
Vent clearance to combustibles is 0 in. Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only. Keep room temp between 32 F (0 C) and 125 F (52 C). Common vent installs: 36 in. top and 24 in. front recommended for service.
Source: Navien NPE-A2/S2 Installation Manual, 3.1 Adequate Installation Clearances, p.17; Outdoor Installation, p.59
Water quality limits and flushing schedule
Water quality · Navien NPE-2
Hardness grains/gal (mg/L) Treatment Flush frequency Soft 0-4 (0-60) None None Moderately hard 4-7 (61-120) None required Once a year Hard 7-9 (121-160) Softener or Navien PeakFlow recommended Once a year Very hard 9-12 (161-200) Softener or PeakFlow highly recommended Residential once a year; commercial twice a year Extremely hard >12 (200) Softener or PeakFlow required -
Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5. Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler. Damage from poor water quality is not covered by warranty. Manual's flush column for moderately hard to hard rows is merged - read as once a year.
Source: Navien NPE-A2/S2 Installation Manual, 3.1 About Water Quality, p.15
Installation clearances (indoor / outdoor)
Clearances · Navien NPN
Side Indoor: combustibles Indoor: non-combustibles Outdoor: combustibles Outdoor: non-combustibles Top 6 in. (152 mm) 2 in. (51 mm) 12 in. (305 mm) 2 in. (51 mm) Back 0 in. 0 in. 0 in. 0 in. Front 6 in. (152 mm) 6 in. (152 mm) Panel 24 in. (610 mm); exhaust 24 in. (610 mm) Panel 0 in.; exhaust 24 in. (610 mm) Sides 2 in. (51 mm) 1/2 in. (13 mm) 6 in. (152 mm) 1/8 in. (3.2 mm) Ground / bottom 12 in. (305 mm) 12 in. (305 mm) 12 in. (305 mm) 2 in. (51 mm) Vent 0 in. 0 in. - -
Room temp must stay between 32 F (0 C) and 120 F (49 C). Outdoor models need a weather-rated disconnect switch for the 120 V supply. Indoor models: rated to 10,100 ft (3,078 m). Outdoor models: under 4,500 ft only.
Source: Navien NPN-U/NPN-E Installation Manual, 3.1 Adequate installation clearances, p.17; 3.6, p.47; 3.7.2, p.49
Models covered NPE-150S2 NPE-180A2 NPE-180S2 NPE-210A2 NPE-210S2 NPE-240A2 NPE-240S2 NPN-120E NPN-160E NPN-160U NPN-180E NPN-180U NPN-199E NPN-199U
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.