Navien · Combi boiler
E001 Heat exchanger overheat
What the control is telling you
The heat exchanger temperature went over its limit and the burner was shut down. NCB-H calls it 'Heat Exchanger Overheat', NFC-H 'heat exchanger over temperature'. NFC-H manual lists the reset type as: Manual reset / Auto reset.
Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)
Likely causes
- Low or no water circulation through the heat exchanger (air in system, closed valves, pump problem)
- Clogged space-heating return filter/strainer
- Scale build-up inside the heat exchanger
Test and repair steps
- Reset from the front panel by pressing the Back button, then confirm the code clears.
- Confirm system pressure and that all heating isolation valves are open; purge air (Installer menu 8. Air Purge Mode > SH pipe air purge).
- Check the boiler pump runs (Installer menu 6. Test Mode > 2. Boiler Pump).
- Clean the space-heating return water filter if heating performance has dropped.
- If it repeats, flush the heat exchanger (see E016).
- Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Minimum installation clearances (indoor) · Navien NCB-H
- Water quality limits (DHW and system fill) · Navien NCB-H
- Minimum installation clearances (indoor) · Navien NFC-H
- Water quality limits (DHW and system fill) · Navien NFC-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.