E046 Heat exchanger thermistor fault
What the control is telling you
The heat exchanger temperature sensor reading is abnormal. Manual action: check the thermistor connector.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Loose, wet or corroded thermistor connector
- Damaged wire
- Failed thermistor
Test and repair steps
- Warning: Turn off power before removing the front cover.
- Reseat the heat exchanger thermistor connector and inspect the wire for damage.
- Compare the temperature readings in Status Info with actual water temperature.
- Replace the thermistor if the fault returns with a good connection.
Settings for these units
- Installation clearances (indoor) · Navien NHB-H
- Installation clearances (indoor) · Navien NFB-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.