Midea · Heat pump
EC5C High pressure sensor failure
What the control is telling you
The outdoor board gets an invalid reading from the high-pressure sensor (transducer). Manual gives meaning only.
Applies to: DLCURAH18-60 AAK/ABK single-zone heat pump outdoor units (18K-60K, regular and High Heat)
Likely causes
- Sensor plug loose
- Damaged sensor wiring
- Failed high-pressure sensor
- Outdoor board fault
Test and repair steps
- Warning: Turn off and lock out power at the outdoor disconnect and wait for the inverter capacitors to discharge before touching the outdoor board or compressor wiring.
- Check the indoor unit display code first - the manual says indoor codes often point to the outdoor problem; see the service manual for detailed tests.
- Reseat the high-pressure sensor connector on the outdoor board.
- Inspect the sensor wiring for damage.
- Compare the sensor reading with a gauge on the service port (refer to the service manual for the sensor output).
- Replace the sensor if faulty; otherwise suspect the outdoor board.
Settings for these units
- Outdoor unit minimum clearances · Midea DLCURA ducted single-zone inverter heat pump (outdoor)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea/Carrier DLCURA Installation Instructions (Catalog DLCURA-03SI), Table 11 Outdoor Unit Diagnostic Codes, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.