Lennox · Heat pump

E422 Compressor top cap switch open

Medium severity

What the control is telling you

Compressor top cap thermal switch exceeded its limit. S30/S40 thermostat alert code 422 (shown as E422 on the unit control display).

Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Condenser fan, TXV or indoor blower problem
  • Stuck reversing valve or clogged filter drier
  • Loose top cap switch wire (XC/XP25)

Test and repair steps

  1. Check condenser fan motor, TXV and indoor blower.
  2. Check for a stuck reversing valve or clogged refrigerant filter.
  3. XC/XP25 make sure both top cap switch wires are on the TP terminals of the outdoor control.
  4. Check superheat and subcooling.
  5. Clears when corrected.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.32. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.