Lennox · Heat pump
40 HP heating lockout
What the control is telling you
The heat pump could not raise room (or zone) temperature 0.5 F toward set point in 30 minutes, so it was locked out and the furnace / electric heat took over (dealer information). S30/S40 thermostat alert code 40.
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Low airflow to the zone(s)
- Heat pump undersized for conditions or low charge
- Balance points set far apart
- Thermostat out of calibration
Test and repair steps
- Check airflow to the zone(s) and the discharge air temperatures.
- Check room thermostat calibration.
- Check HP Heating Lockout Time (default 120 min, range 60-240): S30 Dealer Control Center > Equipment > Smart Hub; S40 Service Support Center > Equipment Settings > Thermostat.
- Dual fuel set high and low balance points close together (about 3 F apart, e.g. 25 F high / 22 F low).
- Check heat pump operation (charge, defrost) if lockouts are frequent.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.13. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.