Lennox · Air conditioner

E429 Inverter DC link low voltage (inverter code 23)

High severity

What the control is telling you

On a compressor call the DC link did not rise above 180 VDC (2- and 3-ton) or 250 VDC (4- and 5-ton) within 30 seconds; unit stops. 10 times in 60 minutes = lockout. Inverter LED flash code 23 (red 2 flashes, green 3 flashes). S30/S40 thermostat alert code 429 (shown as E429 on the unit control display).

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Low input voltage
  • Loose U/V/W connections
  • Failed inverter, filter board or reactor
  • Compressor winding or ground fault

Test and repair steps

  1. Run the thermostat's test function (S30: Dealer Control Center > Tests) and read the inverter's DC link plus line input voltage and current.
  2. Check U, V, W connections at the inverter harness and compressor.
  3. Check compressor winding resistance and compressor to ground; replace compressor if bad.
  4. Check input power single phase 208/230 VAC +10%.
  5. Before you change the inverter, test what is feeding the filter board and reactor.
  6. Measure the DC link and MICOM sensing voltage. Out of range: replace the inverter. In range: the compressor likely has a mechanical problem.
  7. Clears automatically once fixed.
  8. Check inverter LEDs flash code 23 = red 2 flashes, green 3 flashes. Normal inverter LEDs with no fault: red ON, green OFF.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.