E417 Discharge sensor faulty
What the control is telling you
Discharge line temperature sensor open, shorted or out of range (checked after 90 seconds). Escalates after 10 minutes. S30/S40 thermostat alert code 417 (shown as E417 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Failed sensor
- Sensor leads in the wrong pins of the harness connector
Test and repair steps
- Check sensor resistance against the temperature/resistance chart in the unit instructions; replace if out of range.
- Verify harness pin positions against the unit's terminal table; order a replacement cable assembly if the pins are wrong.
- Critical condition power down, replace sensor or cable, power up to clear.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.