FlowMax · Combi boiler
E22 Parameter programming request
What the control is telling you
The board has lost its parameter memory and the parameters must be reprogrammed.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Loss of microprocessor memory
Test and repair steps
- Enter the parameter menu switch OFF, then switch ON while holding '+' and '-' until 'PL' - '0' shows; release.
- Hold 'S' and press '+' to pick a parameter; release 'S', press 'S' again to show the value.
- Set each parameter with '+'/'-' (e.g. P1 water heater type, P2 gas type 00 = natural gas / 01 = propane, P3 heating range) and press 'S' to confirm.
- Switch the unit off and on again so the new settings take effect.
- If memory is lost again, suspect the control board.
Settings for these units
- Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
- Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.10 Troubleshooting table, p.66; FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67; FlowMax FLOWMAX-90 User Manual, Diagnostics - Error codes, p.8-9; FlowMax FLOWMAX-120 Instruction Manual, 5.2 Setting the parameters, p.40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.