25.5 Installer settings corrupted
What the control is telling you
Field installer settings are corrupted; the control runs on default installer settings.
Applies to: Carrier 59SC6A
Likely causes
- Corrupted settings memory
Test and repair steps
- Re-select the installer settings (Ht, CL, Cfn, HoD, Cod, dir, tnn) through the menu.
- If the code stays, reprogram the control with the rating-plate Model Program Number.
- After reprogramming, re-enter the installer settings and verify airflow and temperature rise.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label Information, p.54; Control Board Replacement p.53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.