Carrier · Furnace
23 Pressure switch did not open
What the control is telling you
At the start of a heat call the control found the pressure switch already closed when it should be open.
Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)
Likely causes
- Obstructed pressure tube
- Pressure switch stuck closed
Test and repair steps
- Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
- Check the pressure tubing for blockage or water.
- Check switch continuity with the inducer off; it should be open.
- Replace the switch if stuck closed. Rated break tolerance is +/-0.05 in. W.C. of the nominal value on the label.
- Restart and confirm normal prepurge.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide (cont.), p.89; Sequence of Operation, p.85. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.