AirQuest · Furnace

31 Pressure switch did not close or reopened

High severity

What the control is telling you

The inducer pressure switch did not prove draft.

Applies to: Carrier/ICP-family two-digit status codes — confirm with the code label on the unit

Likely causes

  • Blocked vent or intake
  • Blocked condensate trap / hose
  • Cracked or disconnected pressure switch tubing
  • Weak inducer motor
  • Faulty pressure switch

Test and repair steps

  1. Check vent and intake terminations
  2. Clear the condensate trap and hoses
  3. Inspect pressure switch tubing
  4. Measure draft with a manometer against the switch rating
  5. Replace inducer or switch as indicated

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier/ICP status code label — verify per model. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.